The text in bicsi s tampa fl tdmm can also be found in the national electrical safety code nesc section 320 b 2 separation from other underground installation.
Electrical and data separation.
The electrical wiring will not be affected in any way.
There are four classification levels of susceptibility for cables.
The problem is the possibility of induced noise in the signal or data cable.
The national electrical code nec class 2 and class 3 covers remote control signaling and power limited circuits covered by chapter 7 in article 725.
Unshielded power lines or electrical equipment in proximity to grounded metal conduit pathway.
If open spaced power conductors are used a minimum separation of 50 mm is required.
Air conditioning welding equipment and motors.
Susceptibility in this context is understood to be an indication of how well the signal circuit can differentiate between the undesirable noise and required signal.
They are considered to be a special condition other than a normal power circuit.
Unshielded power lines or electrical equipment in proximity to open or non metal pathways.
Condition 2kva 2 5kva 5kva.
It states separations between supply and communication conduit systems.
I also see this same distance in other specs and publications.
In class 2 and class 3 systems either the voltage or the current depending upon circuit design is limited to a level that will not cause a fire and under.
Minimum separation distance from power source at 480v or less.
All cabling should avoid any proximity to radio or television transmitters beacons and overhead transmission lines.
It follows that a data communication physical standard such as rs 232e would have a high susceptibility and a 1000 v 200 a ac cable has a low susceptibility.
Conduit systems to be occupied by communication conductors shall be separated from conduit systems to be used for supply systems by 75 mm 3 in of concrete 100 mm 4 in of masonry or 300 mm 12 in of well tamped earth.
Power control wiring separation if you are asking separation needed for interference not code we usually use 12 separation between lv signal cabling and line voltage cabling as a general rule.